400 kVA · 320 kW · 50 Hz

400 kVA diesel generator, 320 kW prime

The rating that carries a whole plant: factories, hospitals, data centres and mining camps. Prime 320 kW / standby 352 kW, parallel-ready, containerised or silent canopy.

01What a 400 kVA set is for

Direct answer: a 400 kVA diesel generator delivers 320 kW continuous (prime) at 0.8 pf, 400/230 V 50 Hz, with 440 kVA / 352 kW standby. It suits average loads of 224–256 kW — a full factory, hospital block, mid-size data centre, mining camp or water treatment plant — and is the smallest rating normally supplied parallel-ready for N+1 schemes.
1

Typical applications

  • Factory total standby or prime power
  • Hospital and clinic complexes
  • Data centre block (2 × 400 kVA for N+1)
  • Mining and drilling camps
  • Water treatment and pumping stations
2

Why this rating

  • Largest set that ships in a standard 20 ft container with canopy
  • Fuel burn still manageable without bulk storage
  • Two units give redundancy without a huge footprint
3

When to step up

  • Load above 260 kW average
  • Site above 2000 m altitude
  • Motor starting above 160 kW DOL
  • Regulatory noise limit below 70 dB(A)

02Specification

Indicative configuration — final datasheet issued per order. 60 Hz version available at 480/277 V.

ItemSpecification
Prime power (PRP)320 kW / 400 kVA at 0.8 pf
Standby power (ESP)352 kW / 440 kVA at 0.8 pf
Voltage / frequency400/230 V, 50 Hz, 3-phase 4-wire (480 V / 60 Hz optional)
Engine optionsCummins QSZ13-G3 · Perkins 2206C-E13TAG2 · Weichai WP13 series
AlternatorBrushless, single bearing, IP23, class H, 2/3 pitch for parallel operation
ControllerDeep Sea DSE7320 MKII, ComAp InteliGen or equivalent AMF / parallel controller
Fuel consumption100% load 76 L/h · 75% 57 L/h · 50% 40 L/h
Fuel tank8-hour integral base tank (600 L), lockable, level gauge, drain valve
Noise (silent canopy)75 dB(A) at 7 m
Dimensions (silent)4300 × 1500 × 2200 mm
Weight (silent, wet)≈ 3800 kg
OptionsATS, parallel panel, containerised CSC version, trailer, remote monitoring, fuel polishing, exhaust silencer to 65 dB(A)

Derating: at 2000 m a 400 kVA set behaves like about 352 kVA; at 50 °C ambient like about 384 kVA. Combine both factors when specifying high-altitude or desert sites.

03What 320 kW can carry

Load typeTypical allowanceNote
Mixed plant load224–256 kW average70–80% of prime, allows starting surges
Motor, direct-on-linesingle motor ≤ 160 kWVoltage dip must stay under 15%
Motor, soft start / VFDsingle motor ≤ 220 kWCurrent limited to 2–3× rated
UPS and rectifier load≤ 256 kWCheck THD; 6-pulse UPS needs derating or filter
Parallel pair640 kW prime / N+1 at 320 kWRequires parallel panel and matched alternators

04Export configuration

CE

Compliance

CE with 2000/14/EC noise marking, EPA Tier 4 Final on request, SONCAP (Nigeria), SASO/SABER (Saudi Arabia), EAC (Russia, Central Asia), destination CoC where required.

40

Loading

One silent 400 kVA set per 40 ft HQ container. Containerised CSC version ships as its own shipping unit — practical for remote sites where unloading equipment is limited.

DOC

Documents

English manual, factory load test report with video at 25/50/75/100% load, wiring diagram, packing list, certificate of origin, spare-parts list.

SVC

After-sales

Commissioning guidance, two operators trained, remote diagnostics, wear-parts kit, and a recommended critical spares list for 2000-hour operation.

05Buyer questions

How much load can a 400 kVA generator carry?

320 kW continuous at 0.8 pf. Plan 224–256 kW average for continuous duty. Standby rating is 440 kVA / 352 kW for outage periods. A single motor up to 160 kW can usually be started direct-on-line.

Fuel consumption per hour?

76 L/h at 100% load, 57 L/h at 75%, 40 L/h at 50% — 0.21–0.24 L/kWh. Running 250 kW for 10 hours consumes about 540–600 litres.

Price range?

Indicative FOB China 2026: USD 28,000–42,000 for a silent set. Engine and alternator brand, controller type, and containerised or parallel-ready configuration drive the difference.

Can two units run in parallel?

Yes, with matched alternators, electronic governors and a parallel panel providing synchronisation, load sharing and reverse-power protection. Two sets give 640 kW prime, or N+1 redundancy at loads below 320 kW.

Check the rating against your real load curve

Send the load list and site conditions — altitude, ambient, motor starting method — and we return the calculation plus three configuration tiers.