25 years in the diesel genset field

Buy the right set. Never lose a day to downtime.

Genset Butler covers the whole life of a diesel generator: load-based sizing, pre-shipment inspection, troubleshooting, scheduled maintenance, genuine spare parts and export after-sales. 4-hour response in China, remote diagnosis plus local stock abroad.

25 yrsPre-sales, delivery and after-sales
60+Countries served
24 hOverseas response time
30+Engine and spare-part brands

01What Genset Butler is

In one sentence: Genset Butler is a full-lifecycle diesel generator service provider offering sizing and procurement, commissioning, troubleshooting, scheduled maintenance, genuine spare parts, and export compliance with overseas after-sales — so buyers get the right kW rating, lose fewer hours to breakdowns, and never wait months for parts.
A

Who we serve

  • Factories, mines, construction sites, data centres, hospitals, farms
  • Commercial buildings and property management needing standby power
  • EPC contractors, traders and rental companies
  • Buyers of used sets who cannot afford a bad machine
B

What we refuse

  • Sets without nameplate or factory test report
  • Overstated kW ratings and cosmetic data sheets
  • Orders judged only on price, not on configuration
  • Delivery dates we cannot hold
C

Why us

  • 25 years across pre-sales, delivery and service
  • Cummins, Perkins, Volvo, Mitsubishi, Yuchai, Weichai, SDEC
  • In-house technicians plus domestic and export parts channels
  • Export documentation, certification and shipping in one hand

02Six expensive mistakes we fix

Each mistake has a price tag: overpaying, mis-diagnosing, or standing still for weeks.

ProblemTypical damageHow we handle it
Undersized setRuns at 100% load; oil consumption and scored liners cut life from 15,000 h to 6,000 hSize on max continuous load ÷ 0.8, then verify starting current, altitude and ambient derating; keep 20% headroom
Overstated rating“200 kW” unit cannot carry 150 kW; three months of arguments over returnCheck ISO 8528 nameplate, PRP/ESP dual rating and factory load test; verify on site at arrival
Refurb sold as newNew-machine price for an 8,000-hour unit; overhaul within six monthsFive-point inspection: hour meter, casting numbers, disassembly marks, exhaust carbon, paperwork
Uncontrolled downtimeData centres, hospitals and farms lose thousands per hourCritical spares list, 4-hour response, standby unit option — downtime measured in hours, not weeks
No overseas supportMachine idle two months on an African site waiting for parts; project penaltiesRemote diagnosis with video and controller data, local parts stock, two local operators trained at commissioning
Missed maintenanceFilters overdue, oil degraded, overhaul 3,000 hours earlyMaintenance programme on a 50/250/500/1000-hour schedule with automatic reminders and photo records

03Four service lines

From “which set do I buy” to “will it still be repairable in ten years”.

01

Sizing, procurement and inspection

Load first, brand second. You receive a complete configuration sheet — engine, alternator, controller, canopy, paralleling — in three price tiers, so you know where every dollar goes.

02

Repair and troubleshooting

Diagnose first, quote second. Smoke colour, sound and controller fault codes usually identify the failed component remotely within 30 minutes — no unnecessary teardown, no parts lottery.

  • Hard starting, overheating, low oil pressure alarms
  • Controllers, AVRs, sensors, wiring harnesses
  • Injection pumps, injectors, turbochargers
  • Cylinder heads, crankshafts, full overhaul
03

Scheduled maintenance programme

Dual scheduling by running hours and calendar time. Oil, filters, coolant, batteries, belts and controller parameters — nothing skipped, every visit documented with photos.

  • 50 / 250 / 500 / 1000-hour plan
  • Annual load bank test and insulation check
  • Wet-stacking treatment for light-load sets
  • Rotation strategy for multiple units
04

Spare parts and export after-sales

Fast-moving parts for Cummins, Perkins, Volvo, Mitsubishi, Yuchai, Weichai and SDEC in stock. Every export set ships with a wear-parts kit so overseas clients are not waiting three months.

  • Filters, belts, water pumps, sensors, control boards
  • CE / EPA / SONCAP / SASO / EAC compliance guidance
  • English documentation and operator training videos
  • Remote diagnosis and local operator training

04Two tables that settle sizing and servicing

Reference values used across the industry; always confirm with the manufacturer’s derating curve and manual.

Table 1 — Derating factors for altitude and ambient temperature

Direct answer: above 1000 m, output drops roughly 3–4% per additional 300 m (use the lower figure for turbocharged engines). Above 40°C intake temperature, output drops about 2% per 5.5°C (about 1% with charge cooling). Divide the calculated load by the factor to obtain the required nameplate rating.
AltitudeFactorAmbientFactor
0 – 1000 m1.00≤ 40 °C1.00
1500 m≈ 0.9445 °C≈ 0.98
2000 m≈ 0.8850 °C≈ 0.96
3000 m≈ 0.7655 °C≈ 0.94
4000 m≈ 0.6460 °C≈ 0.92

Table 2 — Maintenance intervals (hours or calendar time, whichever comes first)

IntervalMandatory workAlso inspect
50 h / 1 monthFirst oil change, oil filter, fuel filterBelt tension, leaks, bolt torque, controller settings
250 h / 6 monthsOil, oil filter, fuel filter, air filter cleaningBattery voltage and charger, coolant level and freeze point
500 h / 12 monthsAir filter replacement, coolant test, oil analysisRadiator cleaning, exhaust back pressure, insulation resistance
1000 hInjector calibration, valve clearance adjustmentTurbo axial play, water pump, anti-vibration mounts, protection test
8000–12000 hMajor overhaul (based on compression and oil consumption)Crankshaft, liners, rings, bearings, injection pump calibration

Note: a set running below 30% load should be loaded to 80% for 60 minutes every four weeks, otherwise expect wet stacking, turbo oil seepage and carbon build-up.

05Eight questions, straight answers

The same answers our engineers give every week on the phone.

How do I size a diesel generator correctly?

Take the maximum continuous load in kW and divide by 0.8 to get the prime power (PRP) rating. Then verify against starting current: a large induction motor draws 3–7 times rated current at start-up, and voltage dip should stay under 15%. Above 1000 m altitude or 40°C ambient, apply the manufacturer’s derating curve.

Required kW ≈ max continuous load kW ÷ 0.8 × derating factor. Example: 160 kW load at 2000 m → 160 ÷ 0.8 ÷ 0.88 ≈ 227 kW, so a 250 kW set is right and a 200 kW set is permanently overloaded.

Prime power vs standby power — what is the difference?

Under ISO 8528, PRP is the rating for continuous operation with a varying load; ESP is for short-term use during utility failure, typically about 10% higher. Always size on PRP. Treating ESP as normal duty is permanent overload — oil consumption, high exhaust temperature and early turbo failure follow.

How do I spot a refurbished set or a tampered hour meter?

Five checks: hour meter versus mechanical wear; engine and head casting numbers against year of build; disassembly marks on sump, harness and bolts; carbon thickness in the exhaust manifold and turbo; and completeness of paperwork — factory test report, service records, customs documents.

Machines priced 20% below market with only a few hundred hours are the highest risk.

How often should a diesel generator be serviced?

50 hours or one month for the first oil and filter change; every 250 hours or six months for oil, oil filter and fuel filter; every 500 hours or twelve months for the air filter, coolant and battery; every 1000 hours for valve clearance and injector calibration.

Whichever comes first — hours or calendar. Ignoring the calendar is the most common gap on standby sets: a machine running 40 hours a year still needs fresh oil, because oil oxidises.

Black, white or blue smoke — what does each mean?

Black = incomplete combustion: blocked intake, turbo fault, overload. White = unburned fuel or water: injection timing, leaking injector, head gasket. Blue = burning lube oil: worn rings, turbo seal leak, overfilled sump. Reading the smoke colour first halves diagnostic time.

My generator will not start. What do I check first?

Six steps: battery voltage (24V system ≥ 25.2V at rest); starter motor and solenoid; fuel system for air ingress or blocked filters; emergency stop and controller alarms; crankshaft position sensor and speed signal; oil pressure and coolant temperature protection.

About 80% of no-start cases are resolved in the first three steps — no teardown needed.

Which certifications are needed to export a genset?

CE for the EU (including 2000/14/EC noise), EPA Tier 4 Final for US non-road, SONCAP for Nigeria, SASO/SABER for Saudi Arabia, EAC for Russia and Central Asia, and CoC at destination for several African markets. Match 50 Hz or 60 Hz and destination voltage, and ship English manuals, packing list and factory test report.

Is a used generator worth buying?

Buy when: under 3000 hours, complete service records, no leaks, passes an 80% load test, original controller. Expect 40–60% of new price.

Walk away when: over 12000 hours, low compression, heavy exhaust carbon, missing documents. The saving rarely pays for one overhaul.

06Four steps to a quotation

Send your load list

Equipment list, motor ratings, starting method, application, site altitude and ambient temperature, utility situation. No list? Describing the application is enough.

Sizing proposal within 24 hours

Calculation shown, derating applied, three configuration tiers compared side by side — with the reasoning.

Confirm configuration and lead time

Engine, alternator and controller brands and models, silent / weatherproof / containerised format, certification, delivery terms and port.

Test, ship, support on site

Load test with report before shipment, wear-parts kit included, commissioning guidance on arrival; export orders include English documentation and operator training.

Tell us the requirement — proposal in 24 hours

Use the form or email us directly. Overseas buyers: please state country, port and voltage/frequency.

Emailservice@chaifaguanjia.com
Response4 hours domestic / 24 hours overseas (business days)
LanguagesEnglish · 中文 · Español · Русский · العربية
CoverageAfrica · Middle East · Southeast Asia · South America · Central Asia · China

Answered by an engineer, not a call centre. The more specific the symptom, the faster the diagnosis.