Rating index · 100 – 800 kVA

Pick the rating from the load, not from the price list

Prime kW, standby kW, typical average load and fuel burn for the ratings we ship most, with full specifications for 250, 400 and 500 kVA.

01Rating comparison

Direct answer: kVA × 0.8 = kW at standard power factor. A 250 kVA set carries about 160 kW average load, a 400 kVA set about 250 kW, a 500 kVA set about 320 kW, after keeping 20% headroom for motor starting. Above 2000 m altitude or 45 °C ambient, go one frame size up.
RatingPrime kWStandby kWAvg. loadFuel @100%Typical use
100 kVA808855–65 kW21 L/hShop, small office, house
150 kVA12013284–96 kW32 L/hClinic, restaurant, small plant
250 kVA200220140–160 kW52 L/hFactory, hotel, cold store
400 kVA320352224–256 kW76 L/hHospital, data room, mining camp
500 kVA400440280–320 kW95 L/hMining, cement, large plant
800 kVA640704448–512 kW148 L/hProcessing lines, district cooling

Fuel figures assume 0.21–0.24 L/kWh at full load on a diesel set in good condition. Confirm on the final datasheet — engine family changes the number by up to 8%.

02Detailed specifications

03Sizing questions we get daily

Which rating should I choose?

Max continuous load kW ÷ 0.8 = prime rating, then derate. 250 kVA for 140–160 kW average, 400 kVA for 224–256 kW, 500 kVA for 280–320 kW. Above 2000 m or 45 °C, go one frame up.

How many kVA for a 200 kW load?

200 ÷ 0.8 = 250 kVA at sea level. At 2000 m, divide again by 0.88 → 284 kVA, so specify 300–320 kVA rather than 250 kVA.

Can I use the standby rating as the working rating?

No. Standby power is for outage periods, typically 10% above prime. Running an ESP-rated set continuously means permanent overload and early failure.

Not on the list? Any rating from 20 to 2000 kVA.

Send the load list and site conditions; you get the calculation, three configuration tiers and a FOB price within 24 hours.