Prime kW, standby kW, typical average load and fuel burn for the ratings we ship most, with full specifications for 250, 400 and 500 kVA.
| Rating | Prime kW | Standby kW | Avg. load | Fuel @100% | Typical use |
|---|---|---|---|---|---|
| 100 kVA | 80 | 88 | 55–65 kW | 21 L/h | Shop, small office, house |
| 150 kVA | 120 | 132 | 84–96 kW | 32 L/h | Clinic, restaurant, small plant |
| 250 kVA | 200 | 220 | 140–160 kW | 52 L/h | Factory, hotel, cold store |
| 400 kVA | 320 | 352 | 224–256 kW | 76 L/h | Hospital, data room, mining camp |
| 500 kVA | 400 | 440 | 280–320 kW | 95 L/h | Mining, cement, large plant |
| 800 kVA | 640 | 704 | 448–512 kW | 148 L/h | Processing lines, district cooling |
Fuel figures assume 0.21–0.24 L/kWh at full load on a diesel set in good condition. Confirm on the final datasheet — engine family changes the number by up to 8%.
Most-sold single rating. Cummins 6LTAA8.9, Perkins 1306 or Weichai WP10D. 52 L/h, 72 dB(A), 2600 kg, one per 20 ft container.
Open specification →
Parallel-ready plant rating. Cummins QSZ13, Perkins 2206C or Weichai WP13. 76 L/h, 75 dB(A), 3800 kg, one per 40 ft HQ.
Open specification →
Heavy duty for mining and processing. Cummins QSX15, Volvo TAD1642 or Perkins 2506C. 95 L/h, 76 dB(A), container option.
Open specification →
Max continuous load kW ÷ 0.8 = prime rating, then derate. 250 kVA for 140–160 kW average, 400 kVA for 224–256 kW, 500 kVA for 280–320 kW. Above 2000 m or 45 °C, go one frame up.
200 ÷ 0.8 = 250 kVA at sea level. At 2000 m, divide again by 0.88 → 284 kVA, so specify 300–320 kVA rather than 250 kVA.
No. Standby power is for outage periods, typically 10% above prime. Running an ESP-rated set continuously means permanent overload and early failure.
Send the load list and site conditions; you get the calculation, three configuration tiers and a FOB price within 24 hours.